Juniper QSFP+ 10G LR breakout RX/TX mapping
interface 0 transmits on fiber strand #1 and receives on fiber strand #12
Strand | Router Interface | Interface Rx/Tx |
---|---|---|
1 | 0 | Tx0 (Transmit) |
2 | 1 | Tx1 (Transmit) |
3 | 2 | Tx2 (Transmit) |
4 | 3 | Tx3 (Transmit) |
5 | Unused | Unused |
6 | Unused | Unused |
7 | Unused | Unused |
8 | Unused | Unused |
9 | 3 | Rx3 (Receive) |
10 | 2 | Rx2 (Receive) |
11 | 1 | Rx1 (Receive) |
12 | 0 | Rx0 (Receive) |
Description | Image |
---|---|
Example SM APC MPO to SM UPC LC breakout cable | |
Example SM APC MPO to SM APC MPO | |
Key | |
Male vs Female Coupled connectors must be matched male/female | |
Polarity | |
Couplers | |
Note: Type B/Method B seems to be the standard cable type
Hardware | Requires | Notes |
---|---|---|
PLR4 | MPO/MTP APC Female | Method B/Type B cable to connect MPO breakout boxes to PLR4 |
MPO QSFP+ 4x10G to LC Breakout Box | MPO/MTP APC Female | Method B/Type B cable to connect MPO breakout boxes to PLR4 |
To help item creation:
End A Type | Male/Female (M/F) | APC/UPC | End Z Type | Male/Female (M/F) | APC/UPC | Cable Type | Number of Fiber Strands (F) | Cable Length |
---|
Example:
MPO F APC to MPO F APC Type A 12F 6m = MPO Female pinned APC to MPO Female pinned APC Type A 12 strands 6 meters